PPD CONSTRUCTION ADMINISTRATION PHASE CHECKLIST

PPD REVISED: APRIL 11, 2016
CM/GC SHALL BE RESPONSIBLE FOR FOLLOWING INSPECTIONS AND REVIEWS AND OBTAINING PPD APPROVAL FOR THE BUILDING SUB-SYSTEM FOR SUBSTANTIAL COMPLETION.

 

19

ELEVATORS

  APPROVED FOR SUBSTANTIAL COMPLETION:

(REQUIRED FOR SUBSTANTIAL COMPLETION APPROVAL BY PPD OFFICE.)
 
INSPECTION/REVIEW ITEM
NOTICE REQUIRED
REMARKS
1 Pit inspection 24 hours Pit must be inspected prior to pouring to verify proper moisture seal.
2 Steel casing installation 24 hours  
3 PVC casing installation 24 hours  
4 Jack 24 hours Jack must be inspected before it is put into PVC casing for protection coating
5 Elevator car 24 hours  
6 Oil line 24 hours Oil lines must be continually checked during the installation process
7 Elevator wiring / diagram 72 hours prior to SCI PPD must be provided wiring diagram before SCI
8 Fire alarms recall
Phase I & Phase II
24 hours PPD representative must be present for this testing sequence.
9 State elevator inspection 24 hours PPD representative must be present for this inspection.

 

Download as WORD Doc