PPD CONSTRUCTION ADMINISTRATION PHASE CHECKLIST
PPD REVISED: APRIL 11, 2016
CM/GC SHALL BE RESPONSIBLE FOR FOLLOWING INSPECTIONS AND REVIEWS AND OBTAINING PPD APPROVAL FOR THE BUILDING SUB-SYSTEM FOR SUBSTANTIAL COMPLETION.
14 |
BUILDING FIRE ALARM |
APPROVED FOR SUBSTANTIAL COMPLETION: (REQUIRED FOR SUBSTANTIAL COMPLETION APPROVAL BY PPD OFFICE.) |
|
---|---|---|---|
INSPECTION/REVIEW ITEM |
NOTICE REQUIRED |
REMARKS |
|
1 | Fill out fire alarm data sheet | One week | The items indicated will be checked along with contractor to ensure proper installation and that all PPD standards have been met before signing off this release. |
2 | Test all pull stations Smoke all detectors Check all horns, speakers and lights Check all horns, speakers and lights Check flow switch (if applicable) Check that wiring matches our color code Check that wiring is proper type Run battery test |
One week | Pull down at least one pull station and one detector. Remove wire and check for trouble indication. |
3 | Check FAAP Zone Map Check FAAP for proper operation |
One week | |
4 | Check for FACP protection by a detector Show location of main junction boxes Show physical location of any AUX relays Check that all junction boxes painted red Check to insure that all detectors are readily accessible. Check the remote LEDs for the detectors to insure they are visible. |
One week | This includes AHU shut down, magnetic doors, etc. These relays should be indicated on the prints. |
5 | Field check the accuracy of all documents | One week | |
6 | Turn in all keys, tools, etc. for the system | One week |
Multiple inspections required for large projects